Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
| 06/22/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) BOND GUTTER ENCLOUSER 250-96 2.) SUPPORT WIRES OR CERTAIN TO BE ATTACHED BOTH BOND 300-11 | |
| 05/23/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)NEED TO SEE UNDERGROUND-PLEASE UNCOVER.2)NEED BONDING DEVICES AT SERVICE-BOTHSIDES OF NIPPLE,NIPPLES TO METERS,BOTHSIDES OF CONDUIT FOR GROUND METERS TO DISCONNECT.3)NEED PERMANENT METAL ADDRESS LABELS.4)DOUBLE LUGING AT TERM CAN AND CLEAN SURFAVE UNDERLUG.5)AND METERS GROUND RODS TO BE MIN.6' APART.6)VERTIFY APPROVED USEAGE OF PVC FITTING WITH ENT.7)USE INDEPENDANT SUPPORT WIRES FOR ELECTRIC AS PER CODE 300-11.8)NEED BATH EXHAUST FANS INSTALLED. | |
| 04/26/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) SUPPORT ALL CONDUIT PER 1999 NEC WITHIN 12" OF EACH BOX OR TERMINATION AND EVERY 10' 348-13 NEC 2) INSTALL GROUNDING BUSHINGS THRUOUT SERVICE PER 250-94 NEC 3) INSTALL PERMANENT ADDRESS LABELS FOR METERS, DISCONNECT 4) COMPLETE ROUGH IN BATHROOMS 5) COMPLETE ROUGH IN OFFICE CEILING 6) VERIFY UFER GROUND FOR SERVICE 7) ELECTRICAL NON METALIC TUBING TO COMPLY WITH 331-4 |