Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935* NO WORK PROGRESS A RE INSP. FEE HAS BEEN ASSESSED NOTE: NEED LADDER FOR 2ND ROOF TOP ACCESS | |
| 10/06/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* FINISH PREVIOUS INSPECTION WORK |
|
| 10/04/2000 | ELECTRIC - FINAL | Not ready for Inspection | 10/04/00 NOT READY NO NOTES | |
| 09/18/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* LABEL A/C DISCONNECTS WORKING CLEARENCES IN FRONT OF A/C DISCONNECTS KO SEALS MISSING IDENTIFY GROUND CONDUTOR SUPPORT CONDUIT UNDER SERVICE |
|
| 09/15/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK FINAL UNITS # 102 AND 105 ONLY |
|
| 09/14/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* #101 BOTH RECEPTACLES WIRED WRONG WATER HEATER CONNECTION ANTI OXID COMPOUND ON ALL ALUMIMUM CONDUCTORS MISSING OUTSIDE LIGHT LIGHT SWITCH AT TOP OF STARIS 210-7 (2) 102- GFI LADIES ROOM INCORRECTLY WIRED MISSING SWITCH AND FACE PLATE MISSING WATER HEATER CONNECTION #103- WATER HEATER CONNECTION MISSING FACEPLATE #104 i WATER HEATER CONNECTION #106- MISSING RECEPTACLE AND FACE PLATE LABEL GFI PROTECTED OUTLETS LIGHT SWITCH AT TOP OF STAIRS WATER HEATER CONNECTION #107 WATER HEATER CONNECTION KO SEAL BOTTOM PANEL HAVE BUILDING INSPECTOR VERIFY EXIT SIGNS CHECK ROOF NEXT TIME |