Permit: T99CM04420

Parcel: 11307139A

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/23/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935* NO WORK PROGRESS A RE INSP. FEE HAS BEEN ASSESSED NOTE: NEED LADDER FOR 2ND ROOF TOP ACCESS
10/06/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
FINISH PREVIOUS INSPECTION WORK
10/04/2000 ELECTRIC - FINAL Not ready for Inspection 10/04/00 NOT READY NO NOTES
09/18/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
LABEL A/C DISCONNECTS
WORKING CLEARENCES IN FRONT OF A/C DISCONNECTS
KO SEALS MISSING
IDENTIFY GROUND CONDUTOR
SUPPORT CONDUIT UNDER SERVICE
09/15/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK FINAL UNITS # 102 AND 105 ONLY
09/14/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
#101 BOTH RECEPTACLES WIRED WRONG
WATER HEATER CONNECTION
ANTI OXID COMPOUND ON ALL ALUMIMUM CONDUCTORS
MISSING OUTSIDE LIGHT
LIGHT SWITCH AT TOP OF STARIS 210-7 (2)
102- GFI LADIES ROOM INCORRECTLY WIRED
MISSING SWITCH AND FACE PLATE
MISSING WATER HEATER CONNECTION
#103- WATER HEATER CONNECTION
MISSING FACEPLATE
#104 &#105 WATER HEATER CONNECTION
#106- MISSING RECEPTACLE AND FACE PLATE
LABEL GFI PROTECTED OUTLETS
LIGHT SWITCH AT TOP OF STAIRS
WATER HEATER CONNECTION
#107 WATER HEATER CONNECTION
KO SEAL BOTTOM PANEL
HAVE BUILDING INSPECTOR VERIFY EXIT SIGNS CHECK ROOF NEXT TIME