Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
|
| 02/14/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Correction Required |
ADDTL COMMS - 1. HEADERS ARE REQUIRED TO BE DOUBLE 2 X 8 NOT 2 X 6 BOX BEAMS. 2. 6040 WINDOW REQUIRES DOUBLE 2 X 10 HEADER NOT 2 X 6 BOX BEAM. 3. HEADERS MUST BEAR ON TRIMMERS. 4. STUDS MUST BEAR ON BOTTOM PLATES AND TOP PLATES MUST BEAR ON STUDS. 5. MUD SILL MUST BE NAILED TO RIM JOIST AT 12O.C. 6. STUDS SPACED IN EXCESS OF 24O.C. BY EAST WINDOW AND KITCHEN. |
| 02/14/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999* |