Permit: T99CM04200

Parcel: 14118002E


Addresses:

9800 E RITA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T99CM04200

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/15/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
PANEL NEED'S A 30 A MAIN DISCONNECT
SEPERATE BUILDING TO HAVE ITS OWN GROUND SYTEM 250 NEC
THERE CANNOT BE ANY PIPING BELOW PANEL
THERE NEEDS TO BE A FITTING TO CHANGE FROM PVC TO FLEX AT CONDUIT ABOVE PNL
PUT A LABEL ON PANEL AS TO WERE IT FEEDS FROM
COVER LOOSE ON GFI