Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T99CM04200
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
09/15/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* PANEL NEED'S A 30 A MAIN DISCONNECT SEPERATE BUILDING TO HAVE ITS OWN GROUND SYTEM 250 NEC THERE CANNOT BE ANY PIPING BELOW PANEL THERE NEEDS TO BE A FITTING TO CHANGE FROM PVC TO FLEX AT CONDUIT ABOVE PNL PUT A LABEL ON PANEL AS TO WERE IT FEEDS FROM COVER LOOSE ON GFI |