Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/10/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - PARTIAL - REVISE PLAN PER ITEM 1 OF 11-09-1999 INSPECTION BY FINAL. OKAY TO DRY IN, INSULATE AND DRYWALL. |
| 11/10/1999 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/09/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - DENIED - 1. PLAN SHEET 3 SPECIFIES DETAILS 1/SD2, 13/SD2,15/SD2, 18/SD3, 17/SD3. THIS PLAN SET DOES NOT HANG SHEETS SD-2 OR SD-3. REVISE PLAN AND INDEX. 2. SHEAR WALL 4 REQUIRES ALL ENDS AND EDGES NAILED AT 4 O.C. |
| 11/09/1999 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |