Permit: T99CM04145

Parcel: 12510006A


Addresses:

3689 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T99CM04145

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
03/27/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK TO BACKFILL TRENCH
03/16/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000* THIS INSP WAS FOR RAIN LEADERS AT GARDEN CENTER AND CENTER 6" OVER FLOW ONLY RAIN LEADER WATER TEST OK
03/13/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000* MUST SEE WATER TEST ON OVER FLOW AT NORTH CENTER RAIN HEADERS
03/01/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1) PRIMARY RAIN HEADERS HAVE LEAKS AND HAVE EXCEEDED 135 DEGREES MUST PROVIDE C.O. 2) RE TEST SYSTEM
02/28/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
02/27/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
02/26/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1) PVC 8" RAIN HEADERS CAN NOT BE EXPOSED AT WEST EXTERIOR WALL SEE SEC 313.3 INSTALLATION STANDARDS 94 UPC
2) GAS PRESSURE TEST OK SLEEVE OK FOR GAS LINE TO GENERATOR OK TO BACKFILL TRENCH
3) GAS PRESSURE TEST FOR MAIN GAS LINE ON ROOF
01/29/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
OVERHEAD WATER DISTRIBUTION OK
WATER DISTRIBUTION AIR TEST OK
OK TO INSULATE WATER LINES
CONDENSATE DRAINS ARE STUBBED UP THRU ROOF ONLY OK TO INSULATE
01/22/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
N/H DWV OK IN BATHROOMS ONLY
COPPER IN BATHROOMS OK 100# TEST
OK TO COVER BATHROOM WALLS ONLY