Permit: T99CM04075

Parcel: 103190320


Addresses:

2761 W GORET RD

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
03/14/2000 FRAMING Correction Required ADDTL COMMS - APPROVED AS NOTED: THE EXISTING ROOF LOADS OVER THE GARAGE OPENING AND THERE WAS NO VARIFICATION OF STRUCTURAL CONDITIONS. THIS PROJECT FRAMING IS APPROVED FOR A INFILL OF AN EXISTING GARAGE DOOR OPENING AND NON-BEARING INTERIOR PETITION WALLS ONLY. HOMEOWNER, CONTINUE AT YOUR OWN RISK.
03/08/2000 FRAMING Correction Required ADDTL COMMS - NOT READY - YOU WILL NEED TO REVISE YOUR PLANS TO SHOW AS BUILT. TAKE 2 COPIES TO DEVELOPMENT SERVICES TO HAVE REVISIONS APPROVED. SPECIFICALLY ALL RED STEEL SUBSTITUES FOR WOOD, 1/2 SHEET ROCK AT EXTERIOR.
03/08/2000 FRAMING Not ready for Inspection NOT READY FOR INSPECTION
01/07/2000 FRAMING Correction Required ADDTL COMMS - 1. UNDERSIZE BEDROOM EGRESS WINDOWS. MUST BE A MINIMUM OF 5.7 SQ FEET OF OPENING (PRESENTLY 733 SQ INCH REQUIRED 820 SQ INCH) PLAN CALL FOR 5030 WINDOWS, 4030 INSTALLED. 2. MAXIMUM HEIGHT ALLOWED OF FINISHED WINDOW SILL IS 44 PRESENTLY 45. 3. DRYWALL NOT ALLOWED FOR EXTERIOR WALL USE-PLAN CALLS FOR O.S.B. 4. ONE STUD ON EXTERIOR WALL SPACED IN EXCESS OF 24 O.C. NOTE: INTERIOR WALLS AND ALL ELECTRIC OK. OK TO FINISH INTERIOR WALLS. DO NOT COVER EXTERIOR WALLS.
01/07/2000 FRAMING Denied IVRS - Inspection 0999*