Inspection History Details
Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
Permit Number - T99CM04053
Inspection Description - BUILDING - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2000 | BUILDING - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 05/04/2000 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/1. GFCI ELECTRIC OUTLET REQUIRED WITHIN 24" OF LEFT SIDE OF K. SINK. 2. K. PENUSULA REQUIRES GFCI OUTLET. 3. STOOPS NOT IN EXCESS OF 8" STEP FROM F.F. TO GRADE. 4. WASTE VENT HAS BEEN DRILLED FOR INSTALLATION OF CONDENSATE DRAIN. NOTE: CUT WASTE VENT AT BOTTOM OF DRILLED HOLE. INSTALL A 1 1/2" SANITARY T WITH A 1 1/2" TO 3/4" REDUCER ALL PROPERLY GLUED. 5. PROPERLY SUPPORT A/C CONDENSATE AT 4' O.C. |