Permit: T99CM04046

Parcel: 121123790


Addresses:

1612 N MAGNOLIA AV

Inspection Status: Correction Required

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/28/1999 BUILDING - FINAL Correction Required ADDTL COMMS - INSTALL SCREWS AT PLASTIC CONDUIT CLAMP WHERE NAILS ARE BENT OVER ABOVE SERVICE PANEL.
10/15/1999 BUILDING - FINAL Correction Required ADDTL COMMS - 1. IDENTIFY NEUTRAL FEEDER WITH WHITE TAPE, BOTH ENDS SERVICE AND AT THE SUB-PANEL. 2. CONDUIT: A. WRONG GLUE USED ON PIPE, ONE JOINT HAS SEPARATED ON ROOF. B. CONDUIT TO BE SUPPORTED AT 6 O.C., ROOF, STRAP, OR CLAMP TO BLOCKS. BLOCKS SHOULD BE ATTACHED TO ROOF, MASTIC. C. ATTACH TO SOUTH WALL. 3. IN SERVICE PANEL, STRANDED NEUTRAL, TOO BE IN WG CONNECTION BY ITSELF, MOVE #4 CAN TO GROUND BUSS, ONE WIRE PER TERMINAL. 4. ISOLATE NEUTRAL/GROUND WIRES IN SUB-PANEL, INSTALL CORD. BUSS IF NEUTRAL BAN HAS A GROUND SCREW, REMOVE IT, IT IS TO BE ISOLATED (FLOATING) FROM METER CAN. ALL NEUTRALS TO ISOLATED BAR, ALL BARE, ON CORD. TO CORD BUSS. 5. COOLER NEEDS A MIDWEST, BOX FUSE, PROTECTED.
10/15/1999 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*