Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/LEFT GAS CARD. | |
| 10/02/2000 | MECHANICAL - FINAL | Denied | HOOD CIRCUIT NEEDS N.M. CONNECTOR HOOD IS NOT GROUNDED BAR LIGHT IS NOT GROUNDED PROPERLY U.G. COVERED W/OUT INSPECTION GOINT TO POLE LIGHT OPEN K.O. AT PANEL USE SCH. 80 PVC FOR EXPOSED |
|
| 09/25/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1. UNIT ON ROOF NOT FUSED PROPERLY 2. INSTALL CONDENSATE DRAIN 3. DO NOT USE UNIONS ON GAS LINE ON ROOF. USE REVERSE THREAD NIPPLES 4. INSTALL SERVICE RECEPTACLE 5. CLAMP GAS LINE 6. USE ROOF JACKS ON ELEC PENETRATIONS THRU ROOF 7. USE SEAL TITE ON T-STAT WIRE TO UNIT 8. REMOVE SCREWS FROM INSIDE OF DRYER VENT |