Permit: T99CM04044

Parcel: 136047740


Addresses:

1723 S THAXTON DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/04/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/LEFT GAS CARD.
10/02/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
USE AN APPROVED FITTING ON CONDENSATE TERINATION
PAINT PVC W/LATEX PAINT
REMOVE UNIONS ON GAS PIPE PER SEC 12.11.10 1994 UPC
RETEST ENTIRE GAS SYSTEM
LEVEL A/C UNIT
09/25/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
1. USE A ROOF JACK ON ELEC. CONDUITS PENETRATING THE ROOF
2. CLAMP GAS LINE TO BLOCKS
3. DO NOT USE UNIONS ON GAS LINE ON THE ROOF USE REVERSE THREAD NIPPLE
4. INSTALL CONDENSATE DRAIN
5. INSTALL CAP ON WATER HEATER VENT. USE PROPER SIZE STORM COLLAR AROUND VENT