Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T99CM03999
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2000 | ELECTRIC - TEMPORARY SERVICE | Correction Required | ADDTL COMMS - 1. CLOSE OFF STUB PANELS (2) CANT LOCATE FAULT CURRENTS ON PLAN (3) NEED SEALING LOCKNUTS AT ALL PENETRATIONS ABOVE BUSSING (4) BOND AROUND CONDUIT AT WATER BOND WITH FULL SIZE GROUND TO CONDUIT (5) INSTALL GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR LOCATION | |
01/04/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999* | |
12/30/1999 | ELECTRIC - TEMPORARY SERVICE | Correction Required | ADDTL COMMS - NOT READY AM TO BE RECALLED | |
12/30/1999 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0000* | |
11/16/1999 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection 0000* |