Inspection History Details
Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
Permit Number - T99CM03970
Inspection Description - MECHANICAL - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - ALL CORRECTIONS HAVE BEEN MADE | |
05/23/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - PAY RE-INSPECTION FEE. SMALL CONDENSOR STILL NOT ANCHORED | |
05/23/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935* | |
05/19/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - ANCHOR EQUIPMENT AS PER SEC. 304.4 UMC 1994 | |
05/19/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
05/16/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - CONDENSATE DRAIN TRAP NOT BUILT CORRECTLY 2. INSTALL THREADED PLUG IN SECORDARY DRAIN OUTLET 3. SEAL ALL JOINTS ON METAL DUCT AND PLATFORM 4. ANCHOR CONDENSING UNITS AND REFER LINES 5. LABEL EQUIPMENT PERMANENTLY WITH UNIT NUMBER AND FUSE ACCORDINGLY 6. DUCT TAPE ON REFER LINES NOT ACCEPTABLE | |
05/16/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* |