Inspection History Details
Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T99CM03970
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2000 | PLUMBING - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. ALL CORRECTIONS HAVE BEEN MADE 3. OK TO DRYWALL | |
03/07/2000 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
03/04/2000 | PLUMBING - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. DO WATER TEST ON WASTE AND VENT SYSTEM 2. DRINKING FOUNTAIN @ NORTH SIDE REVENT FITTING IS BACKWARDS. 3. ALL HORIZONTAL ABS VENTS MUST BE STRAPPED OR HUNG EVERY 4 4. 2 & 1 1/2 HORIZONTAL VENTS EXCEED MAXIMUM LENGTH FOR HORIZONTAL RVN | |
03/04/2000 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0000* |