Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T99CM03945

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/03/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - APPROVED - ON 03-30-00 BY D. MANN ON REVISION. REVIEWD BY TERRY STEVENS 03-30-00.
03/28/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - DENIED - SEE SECTION 2326.11.4 OF UBC FOR ALTER NATIVE BRACING AS REQUIRED ALSO ON APPROVED PLANS. FOR SW2 AND SW3.
03/28/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*
02/16/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - PARTIAL - OKAY TO COVER TOP HALF WITH SHEATING. L50 AND L70S INSTALLED AT LEDGERS.
02/16/2000 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*
02/07/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - 1. PLANS CALL FOR L50 & L70 AT LEDGER CONNECTIONS. A35S INSTALLED. PROVIDE APPROVED REVISION FOR AS BUILT. PLAN CALLS FOR H3S TO BE INSTALLED AT LEDGER. H25S ARE INSTALLED. NOTE: IF CONTRACTOR PROVIDES REVISIONS FOR ABOVE, THEN ALL H25S AND A35S WERE INSTALLED AT PARIMETER OF THE HOUSE AND CONTRACTOR MAY CONTINUE WITH OUTSIDE SHEETING TO TOP PLATES.
02/07/2000 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*