Permit: T99CM03944

Parcel: 124052340


Addresses:

801 E 7TH ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T99CM03944

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2000 FRAMING Approved IVRS - Inspection 0000*
09/08/2000 FRAMING Partial Approval IVRS - Inspection 0000*ABOVE CEILING OK TO INSULATE AND DRYWALL. DO NOT COVER LAUNDRY AND SHOWER VALVE AREA. /1. WATER NOT COMPLETE AT INCOMING RISER. 2. LAUNDRY TRAP MUST BE BETWEEN 6" + 18" OF FLLOR. 3. TUB AND SHOWER FIXTURES NOT IN SHOWERS MUST USE TEMP/PRESSURE BALANCED VALVE. 4. W/C FLOOR PLAN GAS MUST BE INSTALLED. 5. BOND GAS AND COPPER PLUMBING W/ #4 BOND WIRE CONNECTED IN VISIBLE LOCATION.
05/23/2000 FRAMING Not ready for Inspection NOT READY FOR INSPECTION