Permit: T99CM03935

Parcel: 13323111Q


Addresses:

7727 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Permit Number - T99CM03935

Inspection Description - ELECTRIC - FINAL

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/28/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - NEED SERV DISC 6X INSTALL MISSING ITEMS 2X GET PHOTO METRIC TO VERIFTY O/S FIX OK FOR LITE CODE
01/28/2000 ELECTRIC - FINAL Partial Approval PARTIAL APPROVAL
01/27/2000 ELECTRIC - FINAL Denied DENIED
01/24/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. ALL DISCONNECTS IN SW BOARD TO BE PERMANENTLY IDENTIFIED 2. CORRECTLY BUTTON UP SECTION UNDER 600A DUSCIBBECT 3. FIND MISSING SECTION AND CLOSE GEAR WITH CORRECT COVER 4. 1 1/4 CONDUIT TO SYSTEM STATUS PNY BRACE WIN 3 OF PNL 5. X-RAY VIEWER TO BE FINISHED 6. SURGERY FIXTURE MISSING TREAT MUST RM 7. X-RAY MACHINE IN X-RAY ROOM MISSING 8. X RAY RM X RAY DISCONNECT SH BE 80 ACB 9. JANITORS RM NEED 350 MCM TO GUTTER? DISCONNECTS NOT READY CONNECT WHS 10 AC UNITS TIE FLEX IN CABINETS ALL OF THRU AND INSTALL COVER ON SERVICE RECEPTACLE 11. SMALL AC UNIT ON FOOF FOR TANK REPLACE 30 A FUSES NEED 20S SEAL HOLE GROUND SW 12. J-BOX BY EAST EXIT DOOR PULLED NOT MADE 13. ALL OUTSIDE WALL FIXTURES TO BE ONLY 50W NOT 150W DUE TO OUTDOOR LIGHTING ORD 8210 14. DISCONNECT TO BATTERY CHARGER TO HAVE 3 CLEARANCE TO GROUNG
01/24/2000 ELECTRIC - FINAL Denied DENIED
01/12/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
01/09/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
12/29/1999 ELECTRIC - FINAL Denied CODE COMPLIANCE CALL OUT
12/22/1999 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
12/17/1999 ELECTRIC - FINAL Correction Required ADDTL COMMS - OK TEMP C OF O PL NO POWER TILL GEAR COMPLETE
12/17/1999 ELECTRIC - FINAL Partial Approval OK FOR TEMP C/O