Inspection Status: Correction Required
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/27/1999 |
EXT METAL CLIPS/EXT SHEATHING |
|
Correction Required |
ADDTL COMMS - SHEAR TRANSFER TO TRUSS AT ENTRY WALL? |
| 09/23/1999 |
EXT METAL CLIPS/EXT SHEATHING |
|
Correction Required |
ADDTL COMMS - 1. O.S.B. ROOF SHEATHING NAILED IN EXCESS OF 6O.C. AT EDGES. 2. ROOF SHEATHING CANNOT BE NAILED WITHIN 3/8 OF EDGES. 3. ROOF SHEATHING NOT NAILED AT BACK EDGE OVER ENTRY. 4. BACKING REQUIRED FOR STUCCO/ROOF FLASHING AT VERTICAL SURFACE OF GABLE TRUSS OVER ENTRY. 5. COLUMN POST/TRUSS NOT CLIPPED AT ENTRY. 6. NAIL PROTECT PLUMBING AT PLATE CUTS. 7. DOUBLE 2X10 HEADERS REQUIRED AT 2 WINDOWS. 2X8 INSTALLED. 8. DRYWALL SHEAR WALLS WITH INTERSECTING INTERIOR WALLS REQUIRE CHANGES NAILED PER U.B.C. PROVIDE ENGINEERS DETAIL. 9. #7 SHEAR WALL LOOSE. NAIL ALL SHINERS. 10.PORCH H 2.5 CLIPS NOT NAILED. 11.HOLD DOWN MISSING AT FRONT OF HOUSE. PROVIDE ENGINEERS APPROVED REPAIR AND CITY OF TUCSON. 12.8/AP NOT COMPLIED WITH. STOPPED INSPECTION. |
| 09/23/1999 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999* |