Inspection History Details
Inspection Status: Correction Required
Inspection History: BUILDING - FINAL
Permit Number - T99CM03773
Inspection Description - BUILDING - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/1999 | BUILDING - FINAL | Correction Required | ADDTL COMMS - NO GAS. | |
10/15/1999 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
10/08/1999 | BUILDING - FINAL | Correction Required | ADDTL COMMS - 1. PAINT ALL ABS ON ROOF AND PVC. 2. A/C DISCONNECT PROVIDE BRACING AND INTERNAL COVER AND 35 AMP FUSES. 3. THERMOSTAT PENETRATION NEEDS CONDUIT COMING OUT OF ROOF JACK THEN CONNECTED TO FLEX CONNECTOR. 4. CONDENSOR FAN WIRING IS EXPOSED OUTSIDE BOX AND NEEDS TO BE CHECKED. 5. NAIL ALL ST22 STRAPS AT POST BEAM CONNECTIONS. 6. PROVIDE SERVICE RECEPT. WITHIN 250 OF A/C UNIT. 7. A/C UNIT DOES NOT WORK. - STOPPED INSPECTION. | |
10/08/1999 | BUILDING - FINAL | Denied | DENIED |