Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/10/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - CORRECTIONS ARE OKAY. |
| 10/14/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. 917/ 5 NOT NAILED AT 4 O.C. TO TRUSS OR TOP PLATE 2. NSILS IN SHEAR WALL 5 DRIVEN TOO DEEP MUST BE FLUSH WITH O.S.B 4. FIRE BLOCK HALL ARCH. 5. MTT28 HOLD DOWN AT BR2 WRONG LOCATION. MUST BEAT OUTSIDE CORNER. RELOCATE OR PROVIDE CITY OF TUCSON AND ENGINEERS APPROVED REVISION. 6. HEADERS MUST BEAR ON TRIMMERS 7. RED HEADS ANCHOR BOLTS LOOSE. TIGHTEN PER ICBO REPORT. 8. INTERIOR NON BEARING WALLS CANNOT BE IN CONTACT WITH BOTTOM CHORD OF SCISSORS TRUSSES. |
| 10/14/1999 |
FRAMING |
|
Denied |
DENIED |