Permit: T99CM03703

Parcel: 130082630


Addresses:

1714 S CHRYSLER AV


Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T99CM03703

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
01/04/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
12/10/1999 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. ALL ELECTRIC BOXES MUST BE MADE UP. 2. SECURE WIRES WITHIN 8 OF ELECTRIC BOXES 3. GROUND ALL METAL ELECTRIC BOXES 4. ELECTRIC OUTLETS ON EXISTING WALL NOT INSTALLED 5. NAIL PROTECT ALL WIRES WITHIN 1 1/4 OF WALL SURFACE 6. BATH GFCI MUST BE ON DEDICATED CIRCUIT 7. COPPER PLUMBING BELOW CEILING BY DOOR 8. UNDERSIZE 4 X 6 BEAM SPANNING 10 5 INDICATED ON PLAN AS EXISTING IS IN FACT NEW 9. EXTERIOR BEARING WALL MUST BE FRAMED WITH STUDS SPACED AT 16 O.C. - PRESENTLY 24 O.C. 10. ADDITION NOT FRAMED PER APPROVED PLAN. BUILD TOPLAN OR REVISE PLAN TO AS BUILT. PLAN MUST BE REACCOMPLISHED TO INDICATE ALL BEAM AND FRAMING MEMBER SIZES. 11. EXPOSE ALL ANCHORS
12/10/1999 ELECTRIC - INTERMEDIATE Denied DENIED
11/01/1999 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0335*