Permit: T99CM03659

Parcel: 10408090C


Addresses:

835 W AUTO MALL DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/01/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/23/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* NOT COMPLETE 1) GROUND WIRE AT COMPRESSOR DISCONNECT USE STAKON
2) ID COMPRESSOR DISCONNECTS 3) DISCONNECT FOR ONE COMPRESSOR DOES NOT HAVE PROPER CLEARANCE IN FRONT OF IT. 4) CANNOT VERIFY LISTING AND APPROVED FOR COMPRESSORS PER NEC 99 SEC 110-3
02/20/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/16/2001 ELECTRIC - FINAL Partial Approval OK FOR TEMP C/O
01/25/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK TO TEMP C OF O SUBJECT TRANSFER OF BOND
01/24/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
ROOF
1. LOOSE FITTINGS
2. BOND ENCLOSERS/DISCONNECTS
3. PROTECT SEALTITE WHERE PASS THROUGH METAL HOLES
4. NEED SIGN INSPECTION
OIL ROOM ELECTRIC WITHIN CLASSIFIED AREA
EXPOSED CONDUTORS OUTSIDE NORTH AND SOUTH SIDE GROUNDS INCORRECTLY MADE UP IN POLE LIGHTS NEED TO SEE ALL EQUIPMENT INSTALLED
01/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
ROOF
1. EXHAUST HOODS NOT WIRED
2. LABEL A/C'S
3. SUPPORT SEAL TITE TO A/C UNITS
4. BOND DISCOUNT ENCLOUSER