Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2001 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
| 12/03/2000 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection 0000* | |
| 12/01/2000 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection 0000* 12/01/2000 OK PANEL "RD" AND "RE" NEED BONDING DEVICE BOTH SIDES OF NIPPLES BOND TRANSFORMER TO SERVICE LABEL DISCONNECT HANDLERS NEED TO SEE MANUFACTURES PAPERWORK REGARDING BRACING AT SERVICE NEED LETTER FROM ENGINEER AUTHORIZING USE OF LUG VS COMPRESSION LUGS NEED LETTER VERFYING TORQUE SETTINGS |