Permit: T99CM03659

Parcel: 10408090C


Addresses:

835 W AUTO MALL DR

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/27/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
BOLLARDS IN FRONT OF ELECTRICAL SWITCH GEAR 1999 NEC SECTION 110-26 SPACES ABOUT ELECTRICAL EQUIPMENT TABLE A CONDITION #1 FOR VOLTAGE TO GROUND 151 V TO 600V BOLLARDS DIRECTLY IN FRONT OF ELECTRICAL SW GEAR TO BE MOVED OUT TO GIVE A COMPLETE CLEARANCE OF 3'6"
BMW BUILDING OUTSIDE FRONT CEILING OK TO COVER
08/08/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
OK NORTH WALL RM 25
OK RECESSED CANS
08/05/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
OK WALLS MESSAGE AND ROOM 25
08/03/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
OK WALLS 20,21,29
PARTIAL WALLS MISSING
08/02/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
PARTIAL WALLS 20,21, OK WALLS 22,18,29
08/01/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
OK WALLS RM 28,30,26,31,32,33,13,14,15,16,17
1. NEED LETTER FROM ENGINEER FOR APPROVAL TO USE M/C CABLE
NOTE RECEP M/C CABLE OUT OF STUD CHANNELS ON VERTICAL RISE