Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* BOLLARDS IN FRONT OF ELECTRICAL SWITCH GEAR 1999 NEC SECTION 110-26 SPACES ABOUT ELECTRICAL EQUIPMENT TABLE A CONDITION #1 FOR VOLTAGE TO GROUND 151 V TO 600V BOLLARDS DIRECTLY IN FRONT OF ELECTRICAL SW GEAR TO BE MOVED OUT TO GIVE A COMPLETE CLEARANCE OF 3'6" BMW BUILDING OUTSIDE FRONT CEILING OK TO COVER |
|
| 08/08/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK NORTH WALL RM 25 OK RECESSED CANS |
|