Permit: T99CM03653

Parcel: 125121580


Addresses:

3352 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
09/29/2000 ROOF NAILING Approved IVRS - Inspection 0000*
09/28/2000 ROOF NAILING Denied WALL SHEATHIN OK NEED TO INSPECT BRICK GAP. 1. ROOF SHEATHING NOT NAILED. 2. PORCH TRUSSES NOT CLIPPED. 3. ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE ENDS AND SPLICES AND EVERY 48" THEREAFTER. 3/8" ANCHOR BOLTS NOT ALLOWED. 4. TOP PLATE SPLICES MUST BEAR ON STUDS. 5. COPPER WATER LINE CANNOT BE IN CONTACT WITH.