Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T99CM03488
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ROOF TOP LOOK GOOD FINAL CONTINGENTION OVER FLOWS BEING DISCHARGED EXCEPTION EVAP CLRS OVERFLOWS HOW OFTEN DOES OVERFLOW DISCHARGE WATER? HOW OFTEN DOES SUMP BLEED IF SUMP DUMPS ON A REGULAR BASIS , DISCHARGE TO WET VENT |
|
07/11/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* | |
06/13/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - 1. A/C 1 CONDENSATE DRAIN SLOPES UPHILL AT TERMINATION. PAINT EXPOSED PVC WITH LATEX PAINT. COMPLETE INSTALLATION OF A/C UNIT. 2. LABEL ALL NEW EQUIPMENT 3. A/C UNIT ON S.E. CORNER CONDENSATE DRAIN CANNOT TRAP AT UNIT AND THEN GO UPHILL TO TERMINATION. WHEN TERMINATING OVER THE TOP OF A WASTE VENT YOU MUST USE A TEE. PAINT PVC W/LATEX PAINT LABEL UNIT 4. FINISH INSTALLATION OF EVAP COOLERS MAKE SURE ALL WORK IS COMPLETE BEFORE CALLING FOR FINAL 5. OLABEL DISCONNECTS AND CORRESPONDING BREAKER | |
06/13/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* | |
04/28/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - 1. PHARMACY IS APPROVED FOR FINAL 2. MEZZANINE IS APPROVED FINAL | |
04/28/2000 | MECHANICAL - FINAL | Partial Approval | OK FOR TEMP C/O | |
04/27/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0950* |