Permit: T99CM03488

Parcel: 110162220


Addresses:

6255 E GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T99CM03488

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
ROOF TOP LOOK GOOD FINAL CONTINGENTION OVER FLOWS BEING DISCHARGED
EXCEPTION EVAP CLRS
OVERFLOWS HOW OFTEN DOES OVERFLOW DISCHARGE WATER?
HOW OFTEN DOES SUMP BLEED IF SUMP DUMPS ON A REGULAR BASIS , DISCHARGE TO WET VENT
07/11/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
06/13/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. A/C 1 CONDENSATE DRAIN SLOPES UPHILL AT TERMINATION. PAINT EXPOSED PVC WITH LATEX PAINT. COMPLETE INSTALLATION OF A/C UNIT. 2. LABEL ALL NEW EQUIPMENT 3. A/C UNIT ON S.E. CORNER CONDENSATE DRAIN CANNOT TRAP AT UNIT AND THEN GO UPHILL TO TERMINATION. WHEN TERMINATING OVER THE TOP OF A WASTE VENT YOU MUST USE A TEE. PAINT PVC W/LATEX PAINT LABEL UNIT 4. FINISH INSTALLATION OF EVAP COOLERS MAKE SURE ALL WORK IS COMPLETE BEFORE CALLING FOR FINAL 5. OLABEL DISCONNECTS AND CORRESPONDING BREAKER
06/13/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
04/28/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. PHARMACY IS APPROVED FOR FINAL 2. MEZZANINE IS APPROVED FINAL
04/28/2000 MECHANICAL - FINAL Partial Approval OK FOR TEMP C/O
04/27/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0950*