Permit: T99CM03488

Parcel: 110162220


Addresses:

6255 E GRANT RD

Inspection Status: Correction Required

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/28/2000 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. RAIN LEADER WATER TEST OK @ COLUMN B 2. OK TO BACKFILL TRENCH
02/17/2000 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. SOIL WATER TEST OK 2. THIS INSPECTION IS FOR PUBLIC RESTROOM @ EAST END OF BLG 3. OK TO BACKFILL TRENCH AFTER HRS INSPECTION FEE PAID IN FULL CK #499447 $177.00
02/17/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
02/15/2000 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. SOIL WATER TEST OK 2. U.G. SOIL OK FOR RM #118 3. OK TO BACKFILL TRENCH 4. WILL REQUIRE REVISED AND APPROVED DRAWING ON COMBINATION WASTE AND VENT SYSTEM BEFORE FINAL.
02/15/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
02/14/2000 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. TAIL PC. OF FIXTURE CAN BE 24 MAX FROM FLOOR LEVEL TO WEIR OF TRAP 2. TAIL PC OF FIXTURE MUST BE AT LEAST 2 PIPE SIZE SMALLER THAN TRAP. 3. RE TEST SYSTEM.
02/14/2000 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0000*