Inspection History Details
Inspection Status: Correction Required
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T99CM03488
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2000 | PLUMBING - ROUGH, SOIL | Correction Required | ADDTL COMMS - 1. RAIN LEADER WATER TEST OK @ COLUMN B 2. OK TO BACKFILL TRENCH | |
02/17/2000 | PLUMBING - ROUGH, SOIL | Correction Required | ADDTL COMMS - 1. SOIL WATER TEST OK 2. THIS INSPECTION IS FOR PUBLIC RESTROOM @ EAST END OF BLG 3. OK TO BACKFILL TRENCH AFTER HRS INSPECTION FEE PAID IN FULL CK #499447 $177.00 | |
02/17/2000 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* | |
02/15/2000 | PLUMBING - ROUGH, SOIL | Correction Required | ADDTL COMMS - 1. SOIL WATER TEST OK 2. U.G. SOIL OK FOR RM #118 3. OK TO BACKFILL TRENCH 4. WILL REQUIRE REVISED AND APPROVED DRAWING ON COMBINATION WASTE AND VENT SYSTEM BEFORE FINAL. | |
02/15/2000 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* | |
02/14/2000 | PLUMBING - ROUGH, SOIL | Correction Required | ADDTL COMMS - 1. TAIL PC. OF FIXTURE CAN BE 24 MAX FROM FLOOR LEVEL TO WEIR OF TRAP 2. TAIL PC OF FIXTURE MUST BE AT LEAST 2 PIPE SIZE SMALLER THAN TRAP. 3. RE TEST SYSTEM. | |
02/14/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0000* |