Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/07/2000 |
ELECTRIC - FINAL |
|
Approved |
|
| 05/10/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - DID NOT LEAVE TILES IN CEILING OPEN TO VIEW H.R. J-BOXES AS INSTRUCTED. (MEZZ) CONDUIT DROPS INTO PHARMACY NOT SUPPORTED VARIOUS LIGHTING POWER CONDUITS AND MC CABLE NOT SUPPORTED BACK TO PANEL OPEN J-BOXES BETWEEN FREEZER AREA AND ELECTRIC ROOM NO PANEL SCHEDULES HOT WATER CIRCULATOR NEED FUSE PROTECTION UNLESS THEIR PROTECTED. |
| 05/10/2000 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/27/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - TEMP C OF O SOUTH ADDITION NOTE: OTHER ELECTRICAL CONTRACTOR TO COVER J-BOXES FOR BATT CHARGERS BEFORE AREA CAN BE OCCUPIED. ABOVE CEILING OK IN NEW MEZZ, LEAVE TILE CRACKED OPEN TO VIEW HR BOX AT LATER TIME |
| 04/27/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
OK FOR TEMP C/O |
| 04/24/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - PARTIAL BATHROOM NOTE: TIGHTEN SET SCREW FITTINGS IN PHARMACY 348-10 |
| 04/24/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |