Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T99CM03488
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2000 | ELECTRIC - FINAL | Approved | ||
05/10/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - DID NOT LEAVE TILES IN CEILING OPEN TO VIEW H.R. J-BOXES AS INSTRUCTED. (MEZZ) CONDUIT DROPS INTO PHARMACY NOT SUPPORTED VARIOUS LIGHTING POWER CONDUITS AND MC CABLE NOT SUPPORTED BACK TO PANEL OPEN J-BOXES BETWEEN FREEZER AREA AND ELECTRIC ROOM NO PANEL SCHEDULES HOT WATER CIRCULATOR NEED FUSE PROTECTION UNLESS THEIR PROTECTED. | |
05/10/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
04/27/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - TEMP C OF O SOUTH ADDITION NOTE: OTHER ELECTRICAL CONTRACTOR TO COVER J-BOXES FOR BATT CHARGERS BEFORE AREA CAN BE OCCUPIED. ABOVE CEILING OK IN NEW MEZZ, LEAVE TILE CRACKED OPEN TO VIEW HR BOX AT LATER TIME | |
04/27/2000 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C/O | |
04/24/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - PARTIAL BATHROOM NOTE: TIGHTEN SET SCREW FITTINGS IN PHARMACY 348-10 | |
04/24/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |