Permit: T99CM03487

Parcel: 11808002M


Addresses:

655 W 22ND ST

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/30/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/27/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/22/2000 ELECTRIC - FINAL Partial Approval AT DISPENSERS AND PUMPS
WILL NEED SEAL OFF FITTING W/IN 18" OF EXP. PROOF ENCLOSURES AND CANNOT USE STANDARD COUPLINGS BETWEEN THE SEAL OFF AND THE EXP PROOF ENCLOSURE.
11/21/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OVERFILL OF CONDUITS ABOVE ROOF (AT ROOF)
ROOF TOP UNFINISHED
LOOSE FITTINGS AT ROOF TOP
USE GROUND BARS TO TERMINATE GROUND WIRES IN ROOF TOP EQUIPMENT DISCONNECTS
OPEN DISPENSER
NEED APPROPRIATE TERMINATING LUG FOR POLES
COMPLETE AIR AND TELEPHONE ELECTICAL
EXTEIOR LIGHTING EG. WALL PACKS TO COMPLY W/ LIGHT POLLUTION CODE. FIXTURES OF MORE THAN 50 WATTS TO BE APPROVED BY PLANS EXAMINER. FIXTURES CHANGES TO 50 W OR LESS NEED TO SUBMITT LETTER STATING THEIR FACT
11/09/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/09/00 NO NOTES
11/08/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OK TEMP POWER FUEL AND TESTING BOND POSTED