Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 11/27/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 11/22/2000 | ELECTRIC - FINAL | Partial Approval | AT DISPENSERS AND PUMPS WILL NEED SEAL OFF FITTING W/IN 18" OF EXP. PROOF ENCLOSURES AND CANNOT USE STANDARD COUPLINGS BETWEEN THE SEAL OFF AND THE EXP PROOF ENCLOSURE. |
|
| 11/21/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OVERFILL OF CONDUITS ABOVE ROOF (AT ROOF) ROOF TOP UNFINISHED LOOSE FITTINGS AT ROOF TOP USE GROUND BARS TO TERMINATE GROUND WIRES IN ROOF TOP EQUIPMENT DISCONNECTS OPEN DISPENSER NEED APPROPRIATE TERMINATING LUG FOR POLES COMPLETE AIR AND TELEPHONE ELECTICAL EXTEIOR LIGHTING EG. WALL PACKS TO COMPLY W/ LIGHT POLLUTION CODE. FIXTURES OF MORE THAN 50 WATTS TO BE APPROVED BY PLANS EXAMINER. FIXTURES CHANGES TO 50 W OR LESS NEED TO SUBMITT LETTER STATING THEIR FACT |
|
| 11/09/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* 11/09/00 NO NOTES |
|
| 11/08/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TEMP POWER FUEL AND TESTING BOND POSTED |