Permit: T99CM03486

Parcel: 125042330


Addresses:

2227 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/10/2002 FRAMING Approved IVRS - Inspection 0000*
11/22/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) PARTIAL ON INTERMEDIATE GROUP PENDING ACCESS PANELS FOR STUD OR VENTS AND TUB GROUT
11/19/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) HOMEOWNER TOOK NOTES
11/15/2001 FRAMING Denied 1) NOT COMPLETE
10/17/2001 FRAMING Denied IVRS - Inspection 0950*/ 1) PLUMBING VENT FOR BATHROOM CANNOT RUN HORIZONTAL UNTIL 42" ABOVE FLOOR-6" ABOVE FLOOD RIM 2) AIR ADMITANCE VALVE CANNOT BE ENCASED IN WALL 3) PEX PLUMBING CANNOT BE JOINED BY HOSE CLAMP 4) STUDS CANNOT EXCEED 24" ON CENTER 5) PLUMBING AND ELECTRIC NOT COMPLETE NOTE: BEARING WALL OK, CANNOT APPROVE UNTIL ALL TRADES COMPLETE
10/12/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*
09/26/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE A COMPLETE SET OF PLANS-PAGE A4 MISSING 2) METAL FRAME BEARING WALL MUST BE BUILT TO REQUIREMENTS OF " PRISCRIPTIVE STANDARDS FOR LIGHT WEIGH METAL FRAME CONSTRUCTION" OR THE INTERNATIONAL RESIDENTIAL BLDG CODE CHAPTER 6 3) ITEM 2, 3, 4, 5, 7, 8, 9 AND 10 FROM 9/18/01 OPEN
09/18/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) REMOVE ALL ELECTRIC SWITCHES AND OUTLETS FOR EXAMINATION OF ELECTRIC BOXES 2) MANY ELECTRIC OUTLETS NOT INSTALLED 3) PLUMBING NOT COMPLETE 4) DRYER MUST HAVE FOUR PRONG OUTLET 5) 14 GAUAGE WIRE NOT ALLOWED IN 20 AMP CIRCUIT 6) ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR 7) CONDUIT LOCK NUTS LOOSE, REQUIRE WASHER, FILL K.O.'S 8) DO NOT MIX WIRE SIZES IN SOME CIRCUITS 9) METAL FRAME BEARING WALL NOT BUILT PER CODE 10) BLOCK MECHANICAL DEFUSER COLLARS 3 SIDES
07/05/2001 FRAMING Not ready for Inspection 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETED