Permit: T99CM03455


Addresses:

7901 S RITA RD

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
02/02/2001 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
PROVIDE ROOF JACKS ON CONDENSATE DRAIN, GAS PIPE, AND ELECTRICAL CONDUITS THRU ROOF
LABEL EQUIPMENT
CAP OFF ABANDONED VENT FLASHING ON ROOF
RAISE SEWER VENT TO 3' ABOVE OUTSIDE AIR INTAKE
USE SCREWS OR RIVETS ON SINGLE WALL VENT INTO DOUBLE WALL
01/30/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*
NEED MIN 1" CLEARANCE AROUND 'B' VENT PENETRATION THUR CEILING AND THUR ROOF SHEATHING
FIRE DAMPERS NEED SHEET ROCK ON BOTH SIDES OF PENETRATION AND ANGLE IRON ON BOTH SIDES
01/19/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
OK FOR GAS CARD
12/01/2000 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
WATER HEATER VENT EXCEEDS ALLOWABLE HORIZONTAL LENGHT YOU CAN GO 75% OF TOTAL VENT HEIGHT.
INSTALL DRYER VENT
USE R6 FLEX DUCT IF DUCT IS ABOVE ATTIC INSULATION
WILL CHECK FIRE DAMPER ACCESS DOORS AFTER CEIING IS INSTALLED OK TO SHEETROCK