Inspection History Details
Permit: T99CM03455
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2001 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000* PROVIDE ROOF JACKS ON CONDENSATE DRAIN, GAS PIPE, AND ELECTRICAL CONDUITS THRU ROOF LABEL EQUIPMENT CAP OFF ABANDONED VENT FLASHING ON ROOF RAISE SEWER VENT TO 3' ABOVE OUTSIDE AIR INTAKE USE SCREWS OR RIVETS ON SINGLE WALL VENT INTO DOUBLE WALL |
|
| 01/30/2001 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection 0999* NEED MIN 1" CLEARANCE AROUND 'B' VENT PENETRATION THUR CEILING AND THUR ROOF SHEATHING FIRE DAMPERS NEED SHEET ROCK ON BOTH SIDES OF PENETRATION AND ANGLE IRON ON BOTH SIDES |
|
| 01/19/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK FOR GAS CARD |
|
| 12/01/2000 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* WATER HEATER VENT EXCEEDS ALLOWABLE HORIZONTAL LENGHT YOU CAN GO 75% OF TOTAL VENT HEIGHT. INSTALL DRYER VENT USE R6 FLEX DUCT IF DUCT IS ABOVE ATTIC INSULATION WILL CHECK FIRE DAMPER ACCESS DOORS AFTER CEIING IS INSTALLED OK TO SHEETROCK |