Permit: T99CM03338

Parcel: 107031480

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/06/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0000*
03/03/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. THE GROUND STRAP ON THE TRANDORMER IS NOT CONNECTED. 2. DID NOT NOTICE BEFORE BUT ONE SIDE OF THE I-BEAM HAS BEEN UTILIZED TO ACT AS ONE PART OF THE TRANSFORMER WALL-THE TRANSFORMER HAS TO BE INSTALLED IN THE FRAME IT CAME IN NOT WELDED TO A SIDE OF I-BEAM. 3. BATHROOM NOT FINISHED. 4. ANY APPROVAL FROM CHANGING 3 PARALLEL SETS OF 750 AC FEEDS TO 500 MCMS? 5. BECAUSE HIGHEST WATTAGE OUTSIDE BULBS CAN BE AT 50 WATTS BECAUSE YOU HAVE UNSHIELDED FIXTURES CITY OUTDOOR ORD.
03/03/2000 ELECTRIC - FINAL Not ready for Inspection NOT READY FOR INSPECTION
01/21/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - DOES NOT APPEAR AS IF ANY WORK ACCORDING TO PLAN HAS BEEN INSTALLED
01/21/2000 ELECTRIC - FINAL Denied DENIED