Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2000 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0000* |
| 03/03/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. THE GROUND STRAP ON THE TRANDORMER IS NOT CONNECTED. 2. DID NOT NOTICE BEFORE BUT ONE SIDE OF THE I-BEAM HAS BEEN UTILIZED TO ACT AS ONE PART OF THE TRANSFORMER WALL-THE TRANSFORMER HAS TO BE INSTALLED IN THE FRAME IT CAME IN NOT WELDED TO A SIDE OF I-BEAM. 3. BATHROOM NOT FINISHED. 4. ANY APPROVAL FROM CHANGING 3 PARALLEL SETS OF 750 AC FEEDS TO 500 MCMS? 5. BECAUSE HIGHEST WATTAGE OUTSIDE BULBS CAN BE AT 50 WATTS BECAUSE YOU HAVE UNSHIELDED FIXTURES CITY OUTDOOR ORD. |
| 03/03/2000 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |
| 01/21/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - DOES NOT APPEAR AS IF ANY WORK ACCORDING TO PLAN HAS BEEN INSTALLED |
| 01/21/2000 |
ELECTRIC - FINAL |
|
Denied |
DENIED |