Permit: T99CM03291

Parcel: 123120070


Addresses:

1501 E SENECA ST


Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Permit Number - T99CM03291

Inspection Description - PLUMBING - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
01/19/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
12/27/1999 PLUMBING - FINAL Correction Required ADDTL COMMS - 1. PLEASE READ PERMIT FOR CORRECT INSPECTION. YOU NEED A INTERMEDIATE PLUMBING INSPECTION. 03035. 2. REAR DOUBLE BATHROOMS, LAYOUT NOT PER PLAN. 3. YOU NEED WORKING H20 PRESSURE ON ALL POTABLE WATER LINES. 4. YOU NEED TO PROTECT ALL PLUMBING PIPES FROM SHEETROCK NAILS. 5. BATHROOM ON WESTSIDE, FRONT IS NOT PER PLAN. THE TOILET IS UNVENTED. REQUIRES A 2 VENT MIN. SHOWER DRAIN. PLUMBING NOT INSTALLED, NEED H20 TEST. 6. 2 PEE TRAP NEXT TO CARPORT. WHAT IS IT FOR? YOU HAVE A LAVATORY ALREADY PLUMBED ON THE LAST WALL? 7. I ONLY FOUND ONE SHEET IN YOUR PLAN SET?
12/27/1999 PLUMBING - FINAL Not ready for Inspection NOT READY FOR INSPECTION