Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T99CM03291
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* | |
12/27/1999 | PLUMBING - FINAL | Correction Required | ADDTL COMMS - 1. PLEASE READ PERMIT FOR CORRECT INSPECTION. YOU NEED A INTERMEDIATE PLUMBING INSPECTION. 03035. 2. REAR DOUBLE BATHROOMS, LAYOUT NOT PER PLAN. 3. YOU NEED WORKING H20 PRESSURE ON ALL POTABLE WATER LINES. 4. YOU NEED TO PROTECT ALL PLUMBING PIPES FROM SHEETROCK NAILS. 5. BATHROOM ON WESTSIDE, FRONT IS NOT PER PLAN. THE TOILET IS UNVENTED. REQUIRES A 2 VENT MIN. SHOWER DRAIN. PLUMBING NOT INSTALLED, NEED H20 TEST. 6. 2 PEE TRAP NEXT TO CARPORT. WHAT IS IT FOR? YOU HAVE A LAVATORY ALREADY PLUMBED ON THE LAST WALL? 7. I ONLY FOUND ONE SHEET IN YOUR PLAN SET? | |
12/27/1999 | PLUMBING - FINAL | Not ready for Inspection | NOT READY FOR INSPECTION |