Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. BLDG H #15 SUPPORT CONDUIT TIGHTEN FITTINGS 2. BLDG I #1 LOCKED 3. BLDG K # SUPPORT CONDUITS 4. BLDG M # 1 LOCKED #5 LOCKED #37 SUPPORT CONDUIT |
| 04/13/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/11/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. CONDUIT BENDS LIMITED TO NOT MORE THAN 4 90 DEGREE BENDS PER N.E.C. 2. CONNECT UFER TO BUILDING STEEL 3. PVC SPACER NOT ACCEPTABLE AS CONDUIT BRACE (USE UNISTRUT ETC.) 4. GROUNDING CONDUTOR LOOSE AT LUG 5. NO ACCESS TO SOME AREAS |
| 04/11/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/17/1999 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |