Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T99CM03220


Addresses:

1575 E 36TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T99CM03220

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2002 ELECTRIC - UNDERGROUND Approved
05/30/2002 ELECTRIC - UNDERGROUND Denied FOR PULL BOXES AND LOAD CENTER. SUPPLY CONDUCTORS CANNOT COME UP THROUGH. SECTION #2, MUST REDO AND INSTALL BARRIER. 1.) LASH SUPPLY CONDUCTORS FROM TRANSFORMER PER INSTRUCTION. 2.) NEED PERMANENT CORRECT ADDRESS AFFIXED TO SERVICE. 3.) PLEASE HAVE AT SITE: COMPANY LETTERHEAD STATING THAT ALL TERMINATIONS HAVE BEEN TORQUED PER MANUFACTURER'S INSTRUCTIONS. 4.) WILL NEED TO VERIFY THAT THE DOWNSTREAM BREAKERS ARE SERIES RATED 'TEY'. 5.) MOVE MAIN GROUNDING ELECTRODE CONDUCTOR TERMINATION TO SECTION NO. 2 AND USE CORRECT WIRE RANGE FOR LUG. 6.) COMPLETE LOAD WIRES AT CONTACTORS 7.) AT POLES. A.) TIGHTEN WIRE NUTS LOOSE. B.) COMPLETELY SEAL ALL TERMINATION EG. GROUNDS, NEUTRALS C.) GROUDNING LUGS LOOSE
04/23/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*PARTIAL FROM COMFORT STA. TO 1ST POLE TO WEST (NEW POLE)
04/18/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*DENIED ( AREA BY COMFORT ST A CONDUIT TOO SHALLOW. COMFRONT STATION DENIED IMPROPER CLEARANCE OF ELECTRICAL EQUIPEMENT AND NO LISTING OF ANY ELECTRICAL W/IN WALK.
04/02/2002 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*NOT READY WILL ALSO NEED BUILD INSP.
03/25/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*SCH 40. PVC (POOR & LITING IN TRENCH OK.
03/15/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* 2" PVC CONTINANCE AT NORTH END APPROVED
03/01/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* 1.) 2" PVC ENTIRE WEST SIDE OF PARK FROM TEP TRANSFORMER QDC #8 TO NW CORNER. FOR SIDE WALK LIGHTING OK TO COVER. 2.) 2" PVC FROM NW CORNER EAST 200' OK TO COVER.
02/28/2002 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*
09/06/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
09/05/2001 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*DENIED UNDERGROUND COVERED LEFT MESSAGE W/N.W. SOUTH SOCCER FIELD SOUTH END, EAST TO WEST LINE UNDERGROUND COMPLETE APPROVED.
09/04/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*OK 2-2" PVC SOUTH END LOWER SOCKER FIELD TO SOUTH END UPPER SOCCER FIELD INCLUDING 2 JUNCTION BOX STUB UP ONLY. OK 2-2" PVC 20 EAST UPPER SOCCER FIELD JUNCTION BOX.
08/31/2001 ELECTRIC - UNDERGROUND Partial Approval
11/17/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
11/14/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
ALL UNDERGROUND EXCEPT MID NORTH SOUTH SECTION
10/17/2000 ELECTRIC - UNDERGROUND Partial Approval TEMP POWER AND TESTING APPROVED.
08/17/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
FROM SOUTH LITE POLE WEST AND NORTH TO LAST (N) LIGHT POLE INTO SES AREA 2" PVC W STEEL 90 DEGREE SWEEPE
08/08/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
BALL FIELD CENTRAL UNDERGROUND AREA COMPLETE
NORTH COMFORT STATION ROMODOR
2" PVC STUBS CAP AND POLE UP STUB
08/03/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
SEVEN POLE BASES INSPECTED
6-IN GROUND BASES PLUS 5'6" TI 6' NO REBAR 40' #2 UFER IN EACH
1-2 1/2" ABOVE GROUND 8' IN GROUND WITH 30" REBAR CAGE AND 40' #2 UFER
AREA PARKING LOT MIDDLE TO SUOTH SECTION OF PARK OK TO POUR
07/13/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
ALL 2" PVC'S S EAST SECTION OF PARK 3 FEET DEEP FEEDERS
07/06/2000 ELECTRIC - UNDERGROUND Not ready for Inspection PLEASE LEAVE APPROVED PLANS AND NOTE AS TO WHERE AND WHAT TO INSPECT. PLEASE RECALL INSPECTION
07/03/2000 ELECTRIC - UNDERGROUND Denied NO ONE ON SITE
06/28/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - CONTINUATION OF CONDUIT THE NORTH AND SOUTH LINES PARALLELING KINO BLVD. (BOTH SIDE OF CENTER SECTION) VARIOUS 2 1 CONDUITS AND STUBS
06/28/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
06/26/2000 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - CENTER SECTION BETWEEN BALL FIELDS EAST/WEST/ IN-UNDERGROND COMPLETE EXCEPT CENTER MANHOLE AREA
06/26/2000 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*