Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T99CM03220
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2002 | ELECTRIC - UNDERGROUND | Approved | ||
05/30/2002 | ELECTRIC - UNDERGROUND | Denied | FOR PULL BOXES AND LOAD CENTER. SUPPLY CONDUCTORS CANNOT COME UP THROUGH. SECTION #2, MUST REDO AND INSTALL BARRIER. 1.) LASH SUPPLY CONDUCTORS FROM TRANSFORMER PER INSTRUCTION. 2.) NEED PERMANENT CORRECT ADDRESS AFFIXED TO SERVICE. 3.) PLEASE HAVE AT SITE: COMPANY LETTERHEAD STATING THAT ALL TERMINATIONS HAVE BEEN TORQUED PER MANUFACTURER'S INSTRUCTIONS. 4.) WILL NEED TO VERIFY THAT THE DOWNSTREAM BREAKERS ARE SERIES RATED 'TEY'. 5.) MOVE MAIN GROUNDING ELECTRODE CONDUCTOR TERMINATION TO SECTION NO. 2 AND USE CORRECT WIRE RANGE FOR LUG. 6.) COMPLETE LOAD WIRES AT CONTACTORS 7.) AT POLES. A.) TIGHTEN WIRE NUTS LOOSE. B.) COMPLETELY SEAL ALL TERMINATION EG. GROUNDS, NEUTRALS C.) GROUDNING LUGS LOOSE | |
04/23/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*PARTIAL FROM COMFORT STA. TO 1ST POLE TO WEST (NEW POLE) | |
04/18/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*DENIED ( AREA BY COMFORT ST A CONDUIT TOO SHALLOW. COMFRONT STATION DENIED IMPROPER CLEARANCE OF ELECTRICAL EQUIPEMENT AND NO LISTING OF ANY ELECTRICAL W/IN WALK. | |
04/02/2002 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000*NOT READY WILL ALSO NEED BUILD INSP. | |
03/25/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*SCH 40. PVC (POOR & LITING IN TRENCH OK. | |
03/15/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 2" PVC CONTINANCE AT NORTH END APPROVED | |
03/01/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 1.) 2" PVC ENTIRE WEST SIDE OF PARK FROM TEP TRANSFORMER QDC #8 TO NW CORNER. FOR SIDE WALK LIGHTING OK TO COVER. 2.) 2" PVC FROM NW CORNER EAST 200' OK TO COVER. | |
02/28/2002 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection 0000* | |
09/06/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
09/05/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*DENIED UNDERGROUND COVERED LEFT MESSAGE W/N.W. SOUTH SOCCER FIELD SOUTH END, EAST TO WEST LINE UNDERGROUND COMPLETE APPROVED. | |
09/04/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 2-2" PVC SOUTH END LOWER SOCKER FIELD TO SOUTH END UPPER SOCCER FIELD INCLUDING 2 JUNCTION BOX STUB UP ONLY. OK 2-2" PVC 20 EAST UPPER SOCCER FIELD JUNCTION BOX. | |
08/31/2001 | ELECTRIC - UNDERGROUND | Partial Approval | ||
11/17/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
11/14/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* ALL UNDERGROUND EXCEPT MID NORTH SOUTH SECTION |
|
10/17/2000 | ELECTRIC - UNDERGROUND | Partial Approval | TEMP POWER AND TESTING APPROVED. | |
08/17/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* FROM SOUTH LITE POLE WEST AND NORTH TO LAST (N) LIGHT POLE INTO SES AREA 2" PVC W STEEL 90 DEGREE SWEEPE |
|
08/08/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* BALL FIELD CENTRAL UNDERGROUND AREA COMPLETE NORTH COMFORT STATION ROMODOR 2" PVC STUBS CAP AND POLE UP STUB |
|
08/03/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* SEVEN POLE BASES INSPECTED 6-IN GROUND BASES PLUS 5'6" TI 6' NO REBAR 40' #2 UFER IN EACH 1-2 1/2" ABOVE GROUND 8' IN GROUND WITH 30" REBAR CAGE AND 40' #2 UFER AREA PARKING LOT MIDDLE TO SUOTH SECTION OF PARK OK TO POUR |
|
07/13/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* ALL 2" PVC'S S EAST SECTION OF PARK 3 FEET DEEP FEEDERS |
|
07/06/2000 | ELECTRIC - UNDERGROUND | Not ready for Inspection | PLEASE LEAVE APPROVED PLANS AND NOTE AS TO WHERE AND WHAT TO INSPECT. PLEASE RECALL INSPECTION | |
07/03/2000 | ELECTRIC - UNDERGROUND | Denied | NO ONE ON SITE | |
06/28/2000 | ELECTRIC - UNDERGROUND | Correction Required | ADDTL COMMS - CONTINUATION OF CONDUIT THE NORTH AND SOUTH LINES PARALLELING KINO BLVD. (BOTH SIDE OF CENTER SECTION) VARIOUS 2 1 CONDUITS AND STUBS | |
06/28/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
06/26/2000 | ELECTRIC - UNDERGROUND | Correction Required | ADDTL COMMS - CENTER SECTION BETWEEN BALL FIELDS EAST/WEST/ IN-UNDERGROND COMPLETE EXCEPT CENTER MANHOLE AREA | |
06/26/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* |