Permit: T99CM03207

Parcel: 125041810


Addresses:

2403 E 2ND ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/30/2004 BUILDING - FINAL Approved IVRS - Inspection :*
11/09/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS
2) TWO ELECTRIC OUTLETS IN BATHROOM CLOSET MUST BE GFCI PROTECTED
3) SMOKE DETECTOR REQUIRED IN BEDROOMS AND AT TOP OF STRAIRS
05/18/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*