Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2000 | MECHANICAL - FINAL | Approved | ALL PENETRATIONS THRU RATED WALL OK | |
| 07/27/2000 | MECHANICAL - FINAL | Partial Approval | 1. LIEBERT UNIT INTO BATTERY RM NEED COMB SMOKE FIRE DAMPER THRU RATED WALL 2. SEAL AROUND RETURN AIR COMB DAMPER SLEEVE AS PER DISCUSSION |
|
| 07/20/2000 | MECHANICAL - FINAL | Denied | 1. ALL PENETRATIONS THROUGH RATED WALL NEED TO BE SEALED INCLUDING CABLE TRAYS 2. KEYED NOTES #4 AUTOMATIC DAMPERS? 3. ROOF TOP UNITS PROVIDE LADDER FOR ACCESS WILL CHECK CONDENSATES, TERMINATION ELECTRICAL PROPER FUSING ETC |
|
| 07/13/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 07/12/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1. NEED APPROVED SET OF PLANS 2. NO PRIOR CALL FOR 3. NO CALL FOR SHEET ROCK PENETRATION INSP PRIOR TO INSTALLING COMB SMOKE FIRE DAMPERS WILL RECALL FOR 07/13/00 |