Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 07/13/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1. STRAP FLEX CONDUIT FOR GENERATOR 2. NEED MAINTANCE RECEPICALE ON ROOF 3. MISSING #2 GROUNDING CONDUTER IN CABLE TRAY 4. HOLE W GUTTER BELOW PANELS 5. FINAL INSPECTION WILL BE HELD UNTIL LIGHTING VIOLATION IS CORRECTED ORDINANCE 8210 SEC 5 |
|
| 07/11/2000 | ELECTRIC - FINAL | Denied | 1. OUTSIDE WALL PACK APPEAR TO BE NEW A. NOT ON PLAN NEED REVISED PLANS B. DO NOT MEET LIGHTING CODE 8210 2. MISSING #2 GROUNDING CONDUTOR IN CABLE TRAY AS PER PLAN NOTE #20 3. WHERE ARE THE RECEPTICLES FOR NOTE #5 4. HOLE IN GUTTER BELOW PANLES 5. NEED ACCESS TO GENERATOR ROOM 6. NEED APPROVED SET OF PLANS ON JOB LOOK AT ROOF NEXT INSP |
|
| 07/10/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* NO ACCESS |