Permit: T99CM03184

Parcel: 117160330


Addresses:

71 E ALAMEDA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/13/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1. STRAP FLEX CONDUIT FOR GENERATOR
2. NEED MAINTANCE RECEPICALE ON ROOF
3. MISSING #2 GROUNDING CONDUTER IN CABLE TRAY
4. HOLE W GUTTER BELOW PANELS
5. FINAL INSPECTION WILL BE HELD UNTIL LIGHTING VIOLATION IS CORRECTED ORDINANCE 8210 SEC 5
07/11/2000 ELECTRIC - FINAL Denied 1. OUTSIDE WALL PACK APPEAR TO BE NEW
A. NOT ON PLAN NEED REVISED PLANS
B. DO NOT MEET LIGHTING CODE 8210
2. MISSING #2 GROUNDING CONDUTOR IN CABLE TRAY AS PER PLAN NOTE #20
3. WHERE ARE THE RECEPTICLES FOR NOTE #5
4. HOLE IN GUTTER BELOW PANLES
5. NEED ACCESS TO GENERATOR ROOM
6. NEED APPROVED SET OF PLANS ON JOB LOOK AT ROOF NEXT INSP
07/10/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0920* NO ACCESS