Permit: T99CM03130


Addresses:

501 E ROGER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/24/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1)SECURE CABLE AND FLEX ABOVE GRID.2)BROKEN PANEL COVER.3)LABEL PANEL AND BREAKERS4)EXPOSED CONDUCTORS.5)LOOSE WEATHER PROOF COVER.6)IF PLUG IS LEFT UNATTENDED USE CORRECT COVER.
04/17/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1. TIGHTEN ALL HARDWARE ON HUBS 2. BOND GUTTER 250-96 3.IDENTIRY CONDUCTORS IN GUTTER 4. TERMINATE ALL CONDUCTORS & IDENTIFY 5. BONDING DEVICE ON RISER 250-94 6. DOUBLE LUGGING AT GROUND BAR 7. IDENTIRY DISCONNECTS & ADDRESS METER 8. TIGHTEN STRUT STRAPS 9. VERIFY SCHED 80 CONDUITS TO DISCONNECTS
06/28/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*