Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/21/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1)SECURE CABLE AND FLEX ABOVE GRID.2)BROKEN PANEL COVER.3)LABEL PANEL AND BREAKERS4)EXPOSED CONDUCTORS.5)LOOSE WEATHER PROOF COVER.6)IF PLUG IS LEFT UNATTENDED USE CORRECT COVER. |
| 04/17/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* 1. TIGHTEN ALL HARDWARE ON HUBS 2. BOND GUTTER 250-96 3.IDENTIRY CONDUCTORS IN GUTTER 4. TERMINATE ALL CONDUCTORS & IDENTIFY 5. BONDING DEVICE ON RISER 250-94 6. DOUBLE LUGGING AT GROUND BAR 7. IDENTIRY DISCONNECTS & ADDRESS METER 8. TIGHTEN STRUT STRAPS 9. VERIFY SCHED 80 CONDUITS TO DISCONNECTS |
| 06/28/2000 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |