Inspection History Details
Inspection Status: Correction Required
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T99CM03095
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/1999 | EXT METAL CLIPS/EXT SHEATHING | Correction Required | ADDTL COMMS - DENIED - STOPPED INSPECTION - TO MANY ITEMS. 1. MISSING ANCHOR BOLTS AT 48O.C. AT EXTERIOR FRAME WALL. 2. CLIP BEAM TO POST. 3. FIREBLOCK WOOD WALL AND CLIP TO BOTTOM PLATE. 4. PROVIDE DETAIL FOR TRIPLE 3X8 BEAM TO MASONRY WALL CONNECTION. 5. GAS BOND CANNOT BE INSIDE WALL _______. 6. PROVIDE NAIL PROTECTION FOR PLUMBING WITHIN 1-1/4 OF WALL SURFACE. 7. BEARING STUD IS CUT BY FURNACE. 8. LEDGER BOLTS ARE MISSING NUTS. 9. JOIST HANGERS ARE MISSING NAILS. 10.BEARING BEAM NOT ANCHORED TO THE WALL WITH 5/8 ABS PER 10A, 10B/A3.4. 11.PLAN CALLS FOR SIMPSON PATM 25 PURLIN ANCHORS. DEFORMED SAT 23 STRAPS WERE USED. PROVIDE ENGINEERING REPAIR. 12.NO WINDOWS. 13.FURNACE VENT MUST TERMINATE 1 FOOT ABOVE PARAPET. | |
11/09/1999 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999* |