Inspection Status: Correction Required
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/10/1999 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. NO APPROVED PLANS ON SITE. 2. BEDROOM WINDOW HAS INADEQUATE EGRESS. WINDOW IS 2-8X4-0 BUT ACTUAL OPENING IS 19X 30 = 570 SQ. IN. 3.9 SQ.FT. REQUIRED OPENING IS 5.7 SQ.FT. UBC 310.4 WITH REMOVAL OF WINDOW WHICH THIS UNIT HAS CAPABILITY OF PULLING 2 SAFETY CLIPS THOUGH 5.0 SQ.FT. IS CAPABLE. NOTE: MECHANICAL AND PLUMBING MEET CODE AND PLAN BUT WILL NOT APPROVE MECHANICAL DUE TO BEDROOM WINDOW EGRESS PROBLEM. OKAY TO INSULATE AND DRYWALL BUT YOU MUST GET AN APPROVED COPY OF PLAN AND APPEAL OF WINDOW EGRESS. |
| 11/10/1999 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 10/20/1999 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. PROVIDE SOFFIT AT LAUNDRY ENTRANCE. 2. BLOCK 3 SIDES ON ALL VENTS 3. NEED APPROVED PLANS 4. BEDROOM WINDOW NOT TO CODE. |
| 10/20/1999 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 10/19/1999 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - INCOMPLETE EXTEND COOLER WATER AND ELECTRIC TO ROOF. BLOCK ALL AIR REGISTERS ON 3 SIDES. CONNECT DUCT TO REGISTER IN LAUNDRY ROOM. RECALL WHEN WORK IS COMPLETE. |
| 10/19/1999 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |