Inspection Status: Correction Required
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/02/1999 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. BLOCK SUPPLY AND RETURN REGISTERS ON 3 SIDES MIN. 2. ADD STRAPS TO BATHROOM FAN DUCTS AT ROOF. 3. MOVE SMOKE DETECTOR MIN 3 AWAY FROM AIR REGISTER IN BEDRM. 2 4. REPLACE TORN ROMEX AT STUDY RM WALL 5. ADD NAIL PLATES AT KITCHEN TOP PLATE TO PROTECT ROMEX. 6. SUPPORT WATER LINE T UP AND AWAY FROM LAUNDRY RM. VENTILATOR FAN. 7. WALL CLEAN OUTS MISSING BATHS 1 AND 2. |
| 09/01/1999 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 2. ADD STRAPS TO BATHROOM FAN DUCTS AT ROOF. 3. MOVE SMOKE DETECTOR MIN. 3 AWAY FROM AIR REGISTER IN BEDRM. 2. |
| 09/01/1999 |
MECHANICAL - INTERMEDIATE |
|
Denied |
DENIED |