Permit: T99CM02830

Parcel: 115011310

Inspection Status: Correction Required

Inspection History: BUILDING - FINAL

Permit Number - T99CM02830

Inspection Description - BUILDING - FINAL

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/24/2000 BUILDING - FINAL Correction Required ADDTL COMMS - APPROVED AS NOTED: FIRE DAMAGE REPAIR.
02/15/2000 BUILDING - FINAL Correction Required ADDTL COMMS - 1. PROVIDE PROOF OF INSPECTION FOR 01030 ROOF NAIL. 2. PROVIDE PROOF OF INSPECTION FOR 02035 ELECTRIC INTERMEDIATE. IF UNABLE TO PROVIDE PROOF OF INSPECTION, THEN EXPOSE. 3. TWO WIRES CANNOT BE CONNECTED TO ONE CIRCUIT BREAKER LUG. 4. FILL ALL HOLES AND KNOCKOUTS THAT ARE NOT FILLED IN SERVICE PANEL DEAD FRONT. 5. SECURE DEADFRONT ON ELECTRIC SERVICE AND LABEL ALL CIRCUITS. 6. GFCI ELECTRIC OUTLET REQUIRED FOR MASTER BATH RIGHT LAVATORY.
02/15/2000 BUILDING - FINAL Denied IVRS - Inspection 0999*
10/06/1999 BUILDING - FINAL Correction Required ADDTL COMMS - NEED ALL PREVIOUS PAPERWORK REGARDING 02035, 01030 APPROVALS
10/06/1999 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*