Permit: T99CM02795

Parcel: 136061530

Inspection Status: Correction Required

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T99CM02795

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/28/1999 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. ALL CORRECTIONS HAVE BEEN MADE 2. OK TO VACKFILL TRENCHES
07/26/1999 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. CAN NOT USE NO HUB COUPLINGS ON PLASTIC. COUPLING MUST BE SPECIALTY COUPLINS WHEN YOU CONNECT ABS TO C.I. 2. OUTLET OF GREASE TRAP HAS OBSTRUCTION OF FLOW @ OUTLET OF TRAP. 3. N.H. COUPLINGS @ OUTSIDE OF BLDG, MUST ALSO BE SPECIALTY COUPLINGS 4. MUST PAY REINSPECTION FEE BEFORE NEXT INSPECTION
07/26/1999 PLUMBING - ROUGH, SOIL Denied DENIED
07/22/1999 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0000*
07/19/1999 PLUMBING - ROUGH, SOIL Correction Required ADDTL COMMS - 1. CAN NOT USE FERMCO COUPLING UNDER SLAB 2. GREASE TRAP MUST HAVE EVEN FLOW @ OUTLET OF TRAP. GALV BUSHING MUST BE REMOVED DUE TO OBSTRUCTION OF FLOW. 3. GREASE TRAP MUST BE VENTED 4. 2 WASTE LINE MUST GO ALL THE WAY TO BAR SINK W/CO @ CHANGE OF DIRECTION 5. 3 COMPT BAR SINK MUST HAVE DRAINAGE FITTING AND STUDOR VENT W/TRAP AND C.O. 6. CAN NOT USE N.H. COUPLING TO CONNECT 2 WASTE LINE FROM B. SINK MUST BE SPECIALTY COUPLING
07/19/1999 PLUMBING - ROUGH, SOIL Denied DENIED