Inspection Status: Denied
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/16/1999 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999* |
| 09/15/1999 |
SHEET ROCK NAILING |
|
Correction Required |
ADDTL COMMS - DENIED STOPPED INSPECTION #1 SHEAR WALLS WITH 1/2 DRYWALL REQUIRE FASTNERS 1 5/8 LONG 1 1/4 INSTALLED AT 7 O.U. GARAGE CEILING NOT COMPLETE 2. # 1 SHEAR WALLS WITH 5/8 DRYWALL REQUIRE 1 7/8 FASTNERS SPACED AT 7 O.C. 1 1/4 INSTALLED. |
| 09/15/1999 |
SHEET ROCK NAILING |
|
Denied |
DENIED |
| 09/11/1999 |
SHEET ROCK NAILING |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |
| 09/07/1999 |
SHEET ROCK NAILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 09/03/1999 |
SHEET ROCK NAILING |
|
Correction Required |
ADDTL COMMS - 1. 1ST LAYER OK |
| 09/03/1999 |
SHEET ROCK NAILING |
|
Partial Approval |
PARTIAL APPROVAL |