Inspection History Details
Inspection Status: Denied
Inspection History: SHEET ROCK NAILING
Permit Number - T99CM02510
Inspection Description - SHEET ROCK NAILING
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/1999 | SHEET ROCK NAILING | Denied | IVRS - Inspection 0999* | |
09/15/1999 | SHEET ROCK NAILING | Correction Required | ADDTL COMMS - DENIED STOPPED INSPECTION #1 SHEAR WALLS WITH 1/2 DRYWALL REQUIRE FASTNERS 1 5/8 LONG 1 1/4 INSTALLED AT 7 O.U. GARAGE CEILING NOT COMPLETE 2. # 1 SHEAR WALLS WITH 5/8 DRYWALL REQUIRE 1 7/8 FASTNERS SPACED AT 7 O.C. 1 1/4 INSTALLED. | |
09/15/1999 | SHEET ROCK NAILING | Denied | DENIED | |
09/11/1999 | SHEET ROCK NAILING | Not ready for Inspection | NOT READY FOR INSPECTION | |
09/07/1999 | SHEET ROCK NAILING | Not ready for Inspection | IVRS - Inspection 0000* | |
09/03/1999 | SHEET ROCK NAILING | Correction Required | ADDTL COMMS - 1. 1ST LAYER OK | |
09/03/1999 | SHEET ROCK NAILING | Partial Approval | PARTIAL APPROVAL |