Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/27/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 07/26/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* G38-40-42 10 AMPS A/C 3 60/40 A/C R1-37-37-41 30.6/45 3- UNITS COND. DRAINS TERMINATE OVER WET VENTS W/TEE NOT 90 DEGREE |
|
| 07/10/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* SEC 310.2 UMC TWO OR MORE CONDENSATE DRAINS TRYING INTO ONE INCREASE COLLECTOR LINE TO 1" 2. SMOKE ALARM SUPPLY DUCT OFF OF AIR HANDLE 3. MICOR SWITCH AIR HANDLER DOORS, WIRED THU HTG CONTROLS. OFF WHEN AIR HANDLER DOOR OPEN 4. RELEIF VALVES RECEIVERS TO DAY LIGHT 5. PERMANENT LABELS ON ROOF DUCT PUMPS AND DISCONNECTS W/CIR BREAKER PANEL NUM 6. COMPLETE HEAT PUMP DATA PLATES |