Permit: T99CM02399

Parcel: 11521151C

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T99CM02399

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2000 ELECTRIC - TEMPORARY SERVICE Approved
07/14/2000 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection 0000*
1. CAN NOT USE SHEET METAL SCREWS FOR GROUND BAR OK TO ENERGIZE SITE LIGHTING PANEL
07/09/2000 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection 0000*
OK TO CLEAR SITE LIGHTING
06/28/2000 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection 0000*
06/23/2000 ELECTRIC - TEMPORARY SERVICE Correction Required ADDTL COMMS - 1. NEED PERMANENT ADDRESS LABEL 2. NEED LETTER VERIFYING TORQUE FOR ASSEMBLE 3. NEED LETTER VERIFYING BARRIER MODIFICATIONS 4. NEED NEUTRAL BARRIER INSTALLED 5. WIRES FOR PANEL SB NOT TO BE TRIMED USE CORRECT WIRE ADAPTOR 6. SUPPORT CONDUTORS IN SWITCH BOARDS WHERE LOOSE
06/23/2000 ELECTRIC - TEMPORARY SERVICE Partial Approval PARTIAL APPROVAL