Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 10/03/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*FINISH ITEMS # 1,4,& 12 OF PREVIOUS INSPECTION. |
| 09/20/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/8' BETWEEN DEVICE AND SURFACE OF BOX. USE AN APPROVED RING. ALSO DO NOT USE COMBUSTABLE MATERIALS FOR SPACES. 2.) PLEASE TIGHTEN GROUND SCREW IN METAL BOX. 3.) ALL SHOP RECPTICALS TO BE GFCI PROJECTED PLEASE LABEL AS SUCH OR PROTECT AS PER CODE. 4.) SPLICES BELOW 18" IN HARZARDOUS AREA TO HAVE SEAL OFFS. 5.) SUPPORT M/C CABLE AS PER CODE 12" 6.) WE HAVE LOOSE M/C FITTINGS AT LIGHTS. 7.) MAINTAIN WORK CLEARANCE FOR A/C DISCONNECT ABOVE OFFICE. 8.) GROUNDING TO JUNCTION BOXES ARE NEEDED 250-148. 9.) AT WATER HEATER TIGHTEN LOOSE FLEX FITTINGS, SUPPORT FLEX AS PER CODE AND INSTALL FUSES. 10.) TIGHTEN AND SUPPORT SEALTITE AT CONDENSING UNIT. 11.) EXHAUST FAN FOR AIR CHANGE IS NOT INSTALLED AT THIS TIME. 12.) WHAT IS SHEILD FOR CUT OFF THAT IS REFERENCE IN PLAN NOTES FOR OUTSIDE LIGHTS? |