Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 09/04/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) WHERE ARE NOTES FOR ELECTRIC SPECS. OK PREVIOUS INSPECTION. |
| 02/08/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK WALLS. 1.) BONDING DEVICES ARE NEEDED ON BOTH SIDES OF THE NIPPLE 250-94. 2.) GROUNDING ELECTRODE INSTALLATION IN NOT COMPLETED. 3.) PLEASE BOND THE SERVICE GUTTER 250-96. 4.) PLEASE FINISH LABELING SERVICES ADDRESS & PANELS 5.) BONDING JUMPER ON SUPPLY SIDE OF SERVICE TO BE SIZED PER CODE 250-102 (C) & 250-66. |