Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T99CM02118
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2000 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* AUTO CARE CENTER MED PRESSURE 60# OK LOW PRESSURE #10 OK ROUGH PIPING OK NEED TO SEE FINAL CONNECTIONS |
|
09/14/2000 | PLUMBING - GAS PRESSURE TEST | Partial Approval | 1. FINAL GAS CONNECTIONS OK, EXCEPT AUTO CARE CENTER WHICH IS OSOLATED BY A SHUTT OFF VALVE. I WILL NEED TO SEE THIS PIPING WHEN IT IS COMPLETE 2. OK TO RENDER GAS |
|
09/01/2000 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection 0000* MED PRESSURE AIR TEST #60 OK DONE PRESSURE AIR TEST 10# OK INSTALL AGA (CSA) VALVE AT TIE IN FROM WELD PIPE TO THREADED OK TO INSTALL PRESSURE REGULATORS |
|
08/31/2000 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection 0000* NEED 60#60 AIR TEST ON MEDIUM PRESSURE AND WELD PIPE NEED GAS VALVE AT TRANSITION FROM WELD PIPE TO SEWER PIPE ALL VALVES MUST HAVE AGA STAMP ON VALVE BODY ROOFER TO INSTALL ISOATORS BETWEEN REDWOOD BLOCKS AND ROOF TOP BEFORE FINAL INSTALL 2 HOLE STRAPS |