Permit: T99CM02118

Parcel: 137276450


Addresses:

1650 W VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T99CM02118

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2000 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
AUTO CARE CENTER MED PRESSURE 60# OK
LOW PRESSURE #10 OK
ROUGH PIPING OK
NEED TO SEE FINAL CONNECTIONS
09/14/2000 PLUMBING - GAS PRESSURE TEST Partial Approval 1. FINAL GAS CONNECTIONS OK, EXCEPT AUTO CARE CENTER WHICH IS OSOLATED BY A SHUTT OFF VALVE.
I WILL NEED TO SEE THIS PIPING WHEN IT IS COMPLETE
2. OK TO RENDER GAS
09/01/2000 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*
MED PRESSURE AIR TEST #60 OK
DONE PRESSURE AIR TEST 10# OK
INSTALL AGA (CSA) VALVE AT TIE IN FROM WELD PIPE TO THREADED
OK TO INSTALL PRESSURE REGULATORS
08/31/2000 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*
NEED 60#60 AIR TEST ON MEDIUM PRESSURE AND WELD PIPE
NEED GAS VALVE AT TRANSITION FROM WELD PIPE TO SEWER PIPE
ALL VALVES MUST HAVE AGA STAMP ON VALVE BODY
ROOFER TO INSTALL ISOATORS BETWEEN REDWOOD BLOCKS AND ROOF TOP
BEFORE FINAL INSTALL 2 HOLE STRAPS